STA 4-Wire SIL 2 and SIL 3 Compliant Programmable Current/Voltage and RTD/Thermocouple Safety Trip Alarms


Get Product Information and Installation Tools
|
Fast Set Up with On-Board Controls
Current
Any range from 0 to 50mA including:
0-20mA
4-20mA
10-50mA
Voltage
Any range from 0 to 10Vdc including:
0-5Vdc
1-5Vdc
0-10Vdc
RTD
2-, 3-, 4-Wire
Platinum, Copper, Nickel
Thermocouple
J, K, E, T, R, S, N, C, B
Ohms
0-4000 ohms
Millivolts
-50 to +1000mV
|
Dual Process Relays and One Fault Relay
Process Relays #1 and #2 individually configure for:
High Alarm
Low Alarm
Normally Open
Normally Closed
Fault Relay #3 configures for:
Normally Open
Normally Closed
Combination Alarm and Transmitter with Optional Analog Output
0-21.6mA
-0.2-10.5V
(The analog output (-AO option) is not part of the safety path, and can not be used as a component in a SIS)
(All relays are fixed as Failsafe)
|
4-Wire
Line-Powered
(24Vdc or Universal for any range between 90-260Vac)
|
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
|
Designed and approved for Safety Instrumented Systems (SIS)
SIL 2 and SIL 3 compliant, third-party certified to IEC 61508
Comprehensive FMEDA certified safety data
Configures using on-board controls
Customizable display shows process status/diagnostics
20-bit input resolution for sensor and analog inputs
Long-term stability, up to five years between calibrations
Optional analog output
|